Current transformer TGE 1-3
Bus-bar CT
![](/fileadmin/_processed_/f/2/csm_TGE1-3_product_image_Produktbild_b52b4f3ee7.jpg)
- Window type for bar
- Moulded in Polyurethane
- Ratio and inner dimension according to custumer specification
- On request with mounting plate and primary busbar
- Standard: IEC/EN 61869-2
- Official calibration possible
Specifications and Downloads
Technical Specifications
TGE1
![](/fileadmin/_processed_/c/c/csm_TGE1_drawing_Massbild_634d60f217.png)
TGE2
![](/fileadmin/_processed_/8/6/csm_TGE2_drawing_Massbild_8cfb109b05.png)
TGE3
![](/fileadmin/_processed_/8/d/csm_TGE3_drawing_Massbild_c64f36a2be.png)
Technical data
Highest operating voltage | 0.72 kV |
Test voltage | 3.0 kV |
Frequency | 50/60 Hz |
Secondary current | 5 or 1 A |
Continuous thermal current | 120 % Ipr |
Short-time thermal current | 60 Ipr 1s |